Fluorescent Light Ballast Repair Replacement, wiring connections (2024)

  • POST a QUESTION or COMMENT about building electrical systems, power, wiring, and flickering or dimming lights

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.


Steps in replacing the ballast or transformer to cure a dead or a flickering fluorescent light.

This article series explains how to diagnose and repair fluorescent lights in buildings.

Watch out: flickering or dimming lights might indicate a dangerous condition risking a building fire or an electrical shock. If the simple bulb or starter repairs we describe here don't cure the flickering, switch off the bad-acting light fixture, leave it off, and ask for help from a licensed electrician.

We also provide an ARTICLE INDEX for this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you need.

Replacing & Wiring a Fluorescent Light Ballast or Transformer

Fluorescent Light Ballast Repair Replacement, wiring connections (1)In the photo I am showing the original data tag for this Fox Co. fluorescent fixture installed in the bathroom of a Minnesota home built in 1963.

[Click to enlarge any image]

To stop the flickering light in this luminaire fixture I needed to replace the ballast.

Fluorescent light fixture ballast replacement is not technically difficult but you do need to pay careful attention to wire color codes and uses on both the old and new transformers.

Watch out: You could be shocked or killed. Turn off electrical power before touching or attempting to work on electrical lights or fixtures.

Watch out: if you are not trained and comfortable with proper electrical wiring and repair work, hire someone who is qualified. Making a mistake can cause a building fire, shock, injury, or death.

Watch out: after electrical power has been removed from the light circuit you must also ground the ballast terminals before touching any wire ends; a ballast can give a tremendous electrical shock.

In concept replacing a fluorescent lamp ballast or transformer is pretty simple; what can be intimidating is the plethora of wiring diagrams on the new ballast, none of which matches exactly the wiring diagram on the original unit.

Ballast manufacturers like Phillips offer technical support, including a telephone number to call for assistance.

Let's sort this out.

Line voltage (typically 120VAC) is supplied to the ballast or transformer.

High voltage output from the transformer connects to the two clip terminals on one end of the fluorescent light bulb.

The other end of the fluorescent light bulb (the two terminals on the clips there) connect to the neutral side of the ballast or transformer and through it back to the circuit neutral.

When we understand those rules we can make sense of otherwise confusing differences among fluorescent lamp transformer wiring diagram differences between the original 50-year old transformer and the new replacement transformer.

Fluorescent Light Ballast Repair Replacement, wiring connections (2)

Two Approaches to light ballast replacement

Watch out: before dis-assembling or removing any lamp parts, label every wire and connection point - and take a few photos too. That can save some embarrassment at re-assembly time.

  1. Find an exact OEM replacement for the original ballast

    You can try to find the exact replacement or a generic replacement light ballast that is asserted to support or replace the original that has failed. There are many such ballast products available from electrical suppliers, hardware stores, building suppliers, and online vendors.

    Some of these replacement ballasts are generic and can support a range of original units besides your particular one.

    You may be able to follow the wiring diagram on your original ballast by identifying the equivalent wires on the new ballast, using just those and capping off any other wires that are not used.

  2. Find a ballast that supports the bulbs and wattages and follow the wiring diagram

    This is what I had to do for this light fixture because an exact OEM replacement transformer was not available.

    You can make note of the wattage of fluorescent bulbs in your light fixture and the number of them, and then purchase a replacement ballast sold to support those. You will need to follow the wiring instructions for the new ballast.

Printing or labels as well as an examination of the wires and connections on all fluorescent light ballasts will provide the following information:

  • Bulb wattage supported
  • Number of bulbs supported
  • Manufacturer and part number
  • Voltage supported
  • A wiring diagram printed right on the ballast surface
  • Physical wires: look at the number of wires and to what they are connected in the current light fixture. Take photos, make a drawing - do not fail to record this information as it makes wiring a new ballast far easier.

Match Replacement Ballast Wiring to Original Ballast Wiring

Below is the old Robertson Transformer Co. ballast from 1963. Note the ballast provides all of the information needed to replace it.

Fluorescent Light Ballast Repair Replacement, wiring connections (3)

  • Ballast catalog no.: CAT. TR-30 416
  • Lamps: One 30-Watt lamp
  • Power: 118V 60 Cy Line amps 0.85
  • Wiring diagram details

The ballast may also tell you the bulb type supported: this bathroom vanity light used 30-W T8 type bulbs.

The light fixture carried two 30-watt fluorescent bulbs, each supported by an individual ballast. However currently it's possible to buy a single ballast that can support two 30-watt bulbs - as another option.

Fluorescent Light Ballast Repair Replacement, wiring connections (4)

Watch out: if you are not trained and comfortable in safe proper electrical wiring procedures do not try to replace the transformer or ballast or other electrical light fixture internal parts yourself. A mistake could result in a fire, or you could be shocked or killed.

The original light fixture used two separate Robertson Transformers, or ballasts, one for each 30-watt lamp.

The replacement ballast, from Triad, was smaller, lighter, (and maybe less durable?) and specified that it could support two 30-watt lamps, simplifying the wiring and replacement job.

Fluorescent Light Ballast Repair Replacement, wiring connections (5)

[Click to enlarge any image]

Watch out: take care to read the wiring diagram on the original ballast and on the replacement ballast to make proper electrical connections.

Some replacement ballasts are designed to handle multiple situations, so you may find that you do not need to use all of the wires on the new ballast. Be sure to use twist-on connectors to cap off any un-used wire ends.

Below: the wiring diagram on the original light fixture ballast or transformer:

Fluorescent Light Ballast Repair Replacement, wiring connections (6)

Watch out: you'll notice that the line voltage (hot - black and neutral - white) 120V wires on the original ballast connect to opposite ends of the ballast: white at one end and black at the other.

Pay close attention to the wiring diagrams and the wire colors. Don't just assume that wires at a particular end of the new ballast have the same functions as on the old ballast. In this case they do not.

Notice also that the "green" wire in the original transformer diagram is NOT a ground wire.

Wires On the Original Ballast / Transformer

  • Black - line hot - wire is at the right end of the transformer where a pair of blue wires emerge.
  • White - line neutral - wire is at the left end of the transformer and is going to connect to one terminal of the fluorescent lamp connector.
  • Green - (NOT a ground wire) in this case is connecting the ballast to the second terminal on the same fluorescent lamp connector as received the white or neutral wire.
  • Blue-1: two blue wires are going to take power to one end of the fluorescent T8 30W lamp circuit or holder. One of these connects to one of the terminals on the opposite end of the bulb from that receiving the green and white wires
  • Blue-2: the second blue wire connected to the other terminal on the same bulb connector as Blue 1.

Wires on the Replacement Ballast / Transformer

Take careful note of the wiring diagram on the new ballast as it will tell you which color coded wires make which connections in the light fixture.

The replacement ballast provides 5 wires: black, white, blue, blue (equivalent) and red.

Fluorescent Light Ballast Repair Replacement, wiring connections (7)

Incoming electrical power at the fixture connects to the line BLACK and WHITE wires shown on the diagram.

If we are using the new ballast to support just one 30W T8 bulb we'd use the red wire connecting to the terminals on one end of the lamp holder/socket and one of the blue wires for the other end of the lamp holder/socket.

If we're wiring two 30W lamps we'd use the second blue wire to take power to that lamp;

The red wire is used in common on both lamps.

I wired the new ballast as shown in the diagram above, following the wire color codes. The light worked perfectly.

See

  • Osram Sylvania, FLUORESCENT LIGHT BALLAST TECHNOLOGY [PDF], retrieved 2018/09/17, original source: https://www.sylvania.com/en-us/innovation/education/light-and-color/Pages/ballasts-technology.aspx
  • Universal Lighting Technologies, BALLAST NAVIGATOR CATALOG [PDF] provides a guide to selecting ballasts for all types of fluorescent light fixtures, Universal Lighting Technologies, TEl: 1-800-BALLAST, Website: https://unvlt.com/literature/ballast-navigator/ produces electronic ballasts for fluorescent light fixtures. Universal produces the Triad® brand of lamp ballasts.

Or read more about fluorescent light fixture ballasts or transformers at our recommended Continue Reading link immediately below.

Reader Comments & Q&A

On 2020-07-12 - by (mod) - match fluorescent bulb ballast to lamp size?

Fluorescent Light Ballast Repair Replacement, wiring connections (8)Eric

Thank you for a helpful question that I'd put as: how closely do I need to match the ballast to bulb types on my fluorescent lights?

Ballasts are "tuned" to start fluorescent bulbs of a particular length. But having replaced a sickening number of fluorescent lamps and ballasts and starters and finding that the exact original replacement is often hard to find, I note that happily there are modern replacement ballast products that very often are rated for a wider range of fluorescent bulbs than their ancestors.

For example, the "Electronic Ballast for F8T5, F11T5, F13T5, F14T5, F21T5 Fluorescent Lamp - HD16/21-120A" - shown below and for sale at Amazon, is marked for both F13T5s AND F14T5s and will work just fine for both.

So let's do this: take a close look at the label on your new ballast. If it indicates it's intended for both F13s and F14s you're fine.

If it's not, it may work OK but you may see poor start-up performance.

On a multi-use or multi-lamp-rated ballast you'll find boht a wiring diagram and often extra wires that you might or might not need to use, dependingon the original fluorescent lamps and fixture being repaired. Just use twist-on connectors to cap off any un-used leads.

Watch out: when you see a delay in turning on fluorescent lamps or bulbs, be sure to check for:

- old fluorescent bulbs that need to be replaced: this may be true even if you don't see that characteristic black or "burned" area near the ends of the bulb

- old, corroded, or loose electrical connectors or connector-to-wire connections in the fluorescent light fixture itself

- a bad starter

So if your lights use them (used on pre-heat type fluorescent lamps or bulbs), also take a look at your starter(s); you'll find a range of them:

FS-2, FS-4, FS-5, FS-12, FS-22, etc. (they're very inexpensive -less than a dollar)

The FS- number refers to the bulb wattage.

but

Watch out: some of the new starters I've bought, made in China, were incredibly flimsy, poorly made, in fact so poorly made that the starter fell apart simply with the push and twist torque necessary to insert and lock the fluorescent lamp starter into its socket.

Fluorescent Light Ballast Repair Replacement, wiring connections (9)

I should have added that even if the ballast appears to work with the "wrong" bulb, an effect may be a reduced bulb life.

On 2020-07-12 by Eric

I recently had to replace a ballast on one of my under cabinet lights in my kitchen. The old ballast was rated for 2 F13T5 bulbs 21”. The new ballast is rated for 2 F14T5 bulbs 21”. Is it okay to use the 2 F13T5 bulbs? The only difference I see this far is when turning on the power source the bulbs take 1 sec to turn on whereas the original turned on immediately.

On 2018-12-10 by Tabatha

I am trying to reconnect the wires on a small one bulb fluorescent light where the wires came off of the ballast
IMAGE LOST by older version of Clark Van Oyen’s useful Comments code - now fixed. Please re-post the image if you can. Sorry. Mod.

Fluorescent Light Ballast Repair Replacement, wiring connections (10)On 2020-01-26 by (mod) - How to re-wire to repairing a fluorescent light desk lamp - Convert to LED bulbs

Thanks for the photos, Scotty.

Beyond the cooked transformers for your desk lamp I see overheated wires all over the place. It's possible that a wire shorted and that cooked the transformers.

If you really want to salvage this light my first choice would be to pull out all of the parts and wires, toss them, and re-wire the lamp for LED bulbs - simpler, much less costly to run, draws far less current (or uses less watts per hour) , even longer bulb life, no flickering, possibly brighter.

When shopping for LED bulbs for fluorescent lamps take care which sort you buy. Some are "plug-and-play" bulbs that don't require any re-wiring but do require a traditional ballast be left in place. Since your lamp parts are all cooked you don't want this option.

A 110-120V F14T8 LED Tube Light-15"-Warm White 3000K bulb looks like the fluorescent bulbs it replaces, plugs into the same bulb socket, but is used WITHOUT the traditional ballast.

When converting to LED, using the original bulb sockets, you will see that each bulb socket will have two wires that are the same color. REmove all 4 of the wires at the socket. On the converted lamp one pin on the socket on one end of the bulb gets the line or "hot" wire and one pin on the socket for the other end of the bulb gets the "neutral" wire.

Watch out: The bulb manufacturer may specify that one particular (marked AC LINE or AC INPUT or similar) end of the LED bulb must connect to the AC HOT or Line side.

There will of course be more wiring details and drawings provided by the LED-Fluorescent bulb replacement manufacturer.

Watch out: if you're not trained on safe electrical wiring get some help from a pro - you could else be shocked or killed or could start a fire.

Below: an LED replacement for a traditional T-8 Fluorescent lamp or bulb, this one from Premier Lighting.

Fluorescent Light Ballast Repair Replacement, wiring connections (11)

On 2020-01-26 by scottygm1959

Fluorescent Light Ballast Repair Replacement, wiring connections (12)

Thank for getting back to me. It seems that the transformers (2) have completely fried, It was working well just a couple days ago, UNTIL, one of the bulbs flashed then went out.

I unplugged the lamp and laid it aside, thinking I could replace the ballast this week, When I unscrewed the base, (see picts) this is what I found,, both of the transformers are little crispy critters,

Any further direction you could give me would be great, I want to restore this lamp to a working condition, I live in the US and have a operating current of 120V the transformer (ballast)? is housed in the base of the lamp.

The wiring seems pretty streight forward.

Will I need 2 ballasts? Thanks

Fluorescent Light Ballast Repair Replacement, wiring connections (13)

On 2020-01-26 by (mod) - Typically a fluorescent desk lamp is about a 15-22-watt device, depending on your country, operating at 120VAC or 220VAC.

Scotty

Thanks for an interesting question. Typically a fluorescent desk lamp is about a 15-22-watt device, depending on your country, operating at 120VAC or 220VAC.

Because the ballast needs to fit into the lamp, probably in the lamp base, it would make the most sense to flip the lamp over, open the base, and photograph the present ballast - then from the ballast label or imprint or stamping we can see its exact specifications, wiring diagram, and we can also see its dimensions. Otherwise you could buy a generic ballast but it may not fit into the lamp.

An example of a typical fluorescent table lamp ballast is the Philips electronic ballasts Table lamp ballasts SBG1X22W/PLN1 is shown below.

Incidentally you might consider converting the lamp from fluorescent to LED - probably more expensive than replacing the ballast but that's an option.

Fluorescent Light Ballast Repair Replacement, wiring connections (14)

The number of fluorescent bulbs you need - if you elect that repair approach for your desk lamp, depends on the ballast selected. Some ballasts can power two or even four bulbs.

The number of bulbs supported by a fluorescent lamp ballast are given on a label or imprint right on the ballast as well as in the installation instructions.

On 2020-01-26 by scottygm1959 - a flexo florescent desk lamp from the '50s and need to replace the transformers, (2), What kind

I have a flexo florescent desk lamp from the '50s and need to replace the transformers, (2), What kind do I need? Thanks!

See the photo now above at the conclusion to this discussion

This Q&A were posted originally at FLUORESCENT LIGHT TRANSFORMER / BALLAST TYPES

On 2019-10-31 by (mod) - 9WPLV/LED/840/DR/4P which requires a ballast with another LED that does not require a ballast?

Re-posting from private email:

Can we replace a

9WPLV/LED/840/DR/4P which requires a ballast with another LED that does not require a ballast? - Anonymous by private email 2019/10/22

Moderator reply:

I've done that successfully in cases where there was a whole string of fluorescent lights in a building, wired in series, operated from a single switch; each light fixture had its own starter and ballast; it was quite possible to replace individual fixtures in that chain without affecting its neighbours.

On 2019-10-22 by Bob electronic ballast for three 30w or 40w rapid start lamps

Looking for a electronic ballast for three 30w or 40w rapid start lamps

On 2019-10-21 by (mod) - T8 fixtures connected together i

I've done what you've described with no problem, assuming I understand your situation correctly.

That is if each light fixture has its own ballast you can change one ballast serving one light fixture without affecting the others.

On 2019-10-20 by Jane F

We have 4 T8 fixtures that are connected together in our kitchen. One of the fixtures burned out and needs to be replaced. Is it safe to put in a newer electronic ballast fluorescent fixture in with 3 older magnetic ballast fixtures. They are all wired together and operate from one wall switch.


...

Continue readingat FLUORESCENT LIGHT TRANSFORMER / BALLAST TYPES or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see these

Recommended Articles

Suggested citation for this web page

FLUORESCENT LIGHT TRANSFORMER / BALLAST REPLACEMENT at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.

Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to ELECTRICAL INSPECTION & TESTING

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia


...

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca

Comment Form is loading comments...

Technical Reviewers & References

Click to Show or Hide Citations & References

  • ...

Books & Articles on Building & Environmental Inspection, Testing, Diagnosis, & Repair

  • Fluorescent Light Ballast Repair Replacement, wiring connections (15)Carson, Dunlop & Associates Ltd., 120 Carlton Street Suite 407, Toronto ON M5A 4K2. Tel: (416) 964-9415 1-800-268-7070 Email: info@carsondunlop.com. The firm provides professional HOME INSPECTION SERVICES and also extensive HOME INSPECTION EDUCATION and home inspection-related PUBLICATIONS. Alan Carson is a past president of ASHI, the American Society of Home Inspectors.

    Thanks to Alan Carson and Bob Dunlop, for permission for InspectAPedia to use text excerpts from The Home Reference Book & illustrations from The Illustrated Home. Carson Dunlop Associates' provides extensive home inspection education and report writing material.

    The ILLUSTRATED HOME illustrates construction details and building components, a reference for owners & inspectors.
    Special Offer: For a 5% discount on any number of copies of the Illustrated Home purchased as a single order Enter INSPECTAILLin the order payment page "Promo/Redemption" space.

    TECHNICAL REFERENCE GUIDE to manufacturer's model and serial number information for heating and cooling equipment, useful for determining the age of heating boilers, furnaces, water heaters is provided by Carson Dunlop Weldon & Associates
    Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on any number of copies of the Technical Reference Guide purchased as a single order. Just enter INSPECTATRGin the order payment page "Promo/Redemption" space.

  • Fluorescent Light Ballast Repair Replacement, wiring connections (16)The HOME REFERENCE BOOK- the Encyclopedia of Homes, Carson Dunlop & Associates, Toronto, Ontario, 25th Ed., 2012, is a bound volume of more than 450 illustrated pages that assist home inspectors and home owners in the inspection and detection of problems on buildings. The text is intended as a reference guide to help building owners operate and maintain their home effectively. Field inspection worksheets are included at the back of the volume.
    Special Offer: For a 10% discount on any number of copies of the Home Reference Book purchased as a single order. Enter INSPECTAHRBin the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

    Or choose the The HOME REFERENCE eBook for PCs, Macs, Kindle, iPad, iPhone, or Android Smart Phones.
    Special Offer: For a 5% discount on any number of copies of the Home Reference eBook purchased as a single order. Enter INSPECTAEHRBin the order payment page "Promo/Redemption" space.

    Fluorescent Light Ballast Repair Replacement, wiring connections (17) Fluorescent Light Ballast Repair Replacement, wiring connections (18) Fluorescent Light Ballast Repair Replacement, wiring connections (19)

  • Building inspection education & report writing systemsfrom Carson, Dunlop & Associates Ltd

    COMMERCIAL BUILDING INSPECTION COURSES - protocol ASTM Standard E 2018-08 for Property Condition Assessments

    HOME INSPECTION EDUCATION COURSES (Canada)

    HOME INSPECTION EDUCATION COURSES (USA) including home study & live classes at eleven colleges & universities.

    HOME INSPECTION EDUCATION: HOME STUDY COURSES - ASHI@Home Training 10-course program.
    Special Offer: Carson Dunlop Associates offers InspectAPedia readers in the U.S.A. a 5% discount on these courses: Enter INSPECTAHITPin the order payment page "Promo/Redemption" space. InspectAPedia.com editor Daniel Friedman is a contributing author.

  • The Horizon Software System manages business operations,scheduling, & inspection report writing using Carson Dunlop's knowledge base & color images. The Horizon system runs on always-available cloud-based software for office computers, laptops, tablets, iPad, Android, & other smartphones
Fluorescent Light Ballast Repair Replacement, wiring connections (2024)

FAQs

How do I replace a ballast wire? ›

  1. Turn electricity off. Go to your breaker box and turn off the power for the area you'll be working on. ...
  2. Remove light cover and bulbs. Often covers can simply be twisted or popped off, but sometimes need to be unscrewed. ...
  3. Remove ballast cover. ...
  4. Disconnect wires. ...
  5. Remove old ballast. ...
  6. Install new ballast.
Jan 9, 2020

What wires connect in a ballast? ›

The ballast has a hot and neutral wire at one end to receive power, and two blue wires a red one at the other end to supply power to the lights.

What colors are ballast wires? ›

2 and 3 lamp instant start ballasts use blue wires for individual connections, and red wires for common connections. Black wire is for line voltage and white wire for neutral. An instant start ballast uses a single wire which connects from the ballast to each of the lamp terminals.

How many wires does a ballast have? ›

The replacement ballast provides 5 wires: black, white, blue, blue (equivalent) and red. Incoming electrical power at the fixture connects to the line BLACK and WHITE wires shown on the diagram.

How do I know if I have T8 or T12? ›

T12 vs T8 Fluorescent Tubes

The main difference between T8 and T12 tubes is the tube's diameter. T12 tubes are 1.5" in diameter while T8s are just one inch. All other things—socket sizes, lengths, distance between pins—are the same.

Which wire is hot on a ballast? ›

Generally, the hot wire on the ballast is black, and the neutral is white. The other colors are the wires that connect the ballast to the fluorescent tube holders and to each other.

What are the yellow wires for on a ballast replacement? ›

Originally Answered: What are the two yellow wire from a ballast for? The two yellow wires are the common connection. you would normally have the yellow connected to one end of a bulb and the other end will be connected to either a blue or a red wire .

How do you wire a 3 wire ballast? ›

Cut and cap one yellow and one red or blue wire with a wire nut. Connect each of the blue ballast wires to the each of the two blue lampholder wires. Connect the red ballast wire to the third blue lampholder wire. Connect the yellow ballast wire to the red lampholder wire.

How are ballasts wired? ›

Individual wires of one ballast connect to the one side of the fixture, individual wires from the other ballast connect to the other side of the fixture. The common wires of each ballast are connected to the other side of the fixture from each of the individual wires.

What is the color code for wire connectors? ›

US AC power circuit wiring color codes

The protective ground is green or green with yellow stripe. The neutral is white, the hot (live or active) single phase wires are black , and red in the case of a second active. Three-phase lines are red, black, and blue.

What happens if you wire a ballast wrong? ›

The ballast is wired to the home's hot, neutral and ground wires on one end, and to the light fixture's lamp holders on the other end. If a ballast fails, it can cause a short, burn out tubes or even cause a fire, so it must be replaced.

What color are line and load wires? ›

The line is usually a black insulated wire that goes to the bottom of the switch while the load is a red wire that goes to the top of the switch. Alternatively, you may use a voltage tester or multimeter to check for a voltage reading from one of the wires.

Can you repair a ballast? ›

It requires having the proper ballast replacement parts, plus knowing how the ballast should be wired. Sometimes, the colour coding on the old ballast does not match the new ballast. We recommend that you always hire a qualified electrician to have a ballast repair or ballast replacement service done.

How do you test a two wire ballast? ›

With your multimeter set to ohm, or “Xl1” if there are multiple ohms on your meter, insert one of the probes into the wire connector containing the white wires. Touch the other end to the remaining blue, red, and/or yellow wires attached to the ballast. Your multimeter won't move if your ballast has gone bad.

What are the parts of fluorescent ballast? ›

Compact fluorescent components consist of cover, coil glass tube, phosphor coating, mercury vapor, ballast, ballast cover, and base.

Can I put a T8 bulb in a T12 ballast? ›

T8 LED lamps which are not direct-wire compatible (with ballast) will require a T8 ballast to operate, so unless the T12 ballast in the T12 fixture is replaced with a T8 ballast, a non-direct-wire compatible T8 LED lamp will not work in a T12 fixture.

Can I replace a T12 ballast with a T8? ›

The easiest and lowest price option to replace a T12 is a T8 linear fluorescent. They have become the go-to option for pre-existing T12s. If you still have magnetic ballasts, switching to a T8 will require a ballast swap.

Can I put a T8 in a T12 fixture? ›

Is it safe to use T-8 bulbs instead? A T8 in a T12 fixture will not light, don't try!

What is a red and white wire on a ballast? ›

Yes, in North America on a fluorescent ballast, white is neutral and black is hot -- switched hot, that is. In North American wiring, white and gray are neutral, green and yellow/green are safety ground, and everything else is hot. So red is hot.

What color does the hot wire go to? ›

The black wire is the "hot" wire, it carries the electricity from the breaker panel into the switch or light source. The white wire is the "neutral" wire, it takes any unused electricity and current and sends it back to the breaker panel.

What is the yellow wire in old wiring? ›

Yellow Wires – always assume they are live if you have power. A yellow wire is used as a live wire pulled through a conduit. You'll find yellow wires used in fixtures like lighting and ceiling fans. Blue Wires – always assume they are live if you have power.

What is a yellow and white wire in electrical? ›

Yellow wires are almost always used as switch legs for outlets, fans, or lights. White or Gray. White or gray indicates a neutral wire, which provides the return path for the current carried by the hot wires and is grounded within the electrical panel.

What is a yellow and green wire for? ›

The green and yellow wire is also referred to as the earth wire and has a key safety function. Electricity being transferred around any property will always take the path of least resistance to the earth.

Is ballast bypass the same as direct wire? ›

Bypass the ballast linear LEDs – also known as line voltage or direct-wire linear LEDs – work straight off the line voltage flowing directly to the sockets, requiring you to remove the original fluorescent ballast.

How many wires must be run between a fluorescent ballasts and its dimmer control? ›

Two-wire controlled ballasts have two wires between the dimmer control and the ballast: Dimmed Hot and Neutral (Fig. 1).

Does a ballast need to be grounded? ›

Ballasts must be connected to electrical ground to avoid electrical shock or damage to the equipment and facility.

What voltage comes out of a ballast? ›

The reading should be between 300 and 1000 volts depending on the ballast model.

What happens if you bypass a ballast? ›

Safety risk The most significant negative to a ballast-bypass linear LED is the risk of electric shock since the sockets carry line voltage. It's a common practice to place a finger on the lamp pins while you are trying to install it, and this becomes a risky endeavor when using single-ended ballast-bypass lamps .

Which wire connectors should you use? ›

Lever-nuts are the “Best” option because of all of the benefits they offer over both twist-ons and push-ins. Although they're the most expensive option (perhaps making them cost-prohibitive to many professionals) their benefits make them ideal for do-it-yourselfers and novices especially.

Is my ballast magnetic or electronic? ›

Method One - Use your smart phone camera. Stand under the light or a place close to the light and point your cell phone camera at the light. If you can see some strong dark strips flickering in your camera, it must be a magnetic ballast based light. Otherwise it should be an electronic ballast based light.

Can you hook up a ballast resistor backwards? ›

Resistors lack polarity. There is no backwards. Save this answer.

Can you bypass a ballast on a fluorescent light? ›

If the existing fluorescent tube fixture you want to replace has a non-shunted tombstone, you can proceed with the ballast bypass procedure. Nonetheless, if the existing fixture offers a shunted tombstone, you should replace it with a non-shunted variant.

Do I connect to line or load? ›

The line side of an outlet is where you connect the incoming source power. The load side is where the power leaves the device (or electrical box) and travels down the circuit.

How do you know which wire is line or load? ›

Determine the position of the wires.

Line wires are always connected to the electrical panel from the bottom. Whereas, load wires are always connected from the top. So by simply looking at the position of the connected wires on the circuit, you'll be able to differentiate between the two wires in the panel.

What happens if you switch line and load wires? ›

With simple on-off light switches, mixing up the line and load wires won't affect the operation. The power will be either off or on. It does become critical is when installing a GFCI outlet. Because it contains an internal circuit breaker, incorrect installation can cause a safety failure.

How much does it cost to replace an electrical ballast? ›

A replacement ballast costs about $10-25 depending on capacity and brand. The bite is that an electrician trip charge (which includes 30 or 60 minutes work) is going to be $75-150 probably - for about 5 minutes work on each light fixture.

Where does the yellow wire go on a ballast? ›

The common yellow wires connect from the ballast to push-in connectors on one of the right holders of lamp 1 or 2. Two yellow wires connect the common lampholders together.

Can a ballast be bypassed? ›

When bypassing the ballast, you may need to change your sockets from the most common shunted sockets to non-shunted sockets. Non-shunted sockets are required if you're using single-ended tubes. This will require a small amount of additional material cost and more labor to replace them all.

What is the lifespan of a ballast? ›

The average life expectancy of a fluorescent light ballast is 10-15 years. Any ballast beyond that age should be considered to be at a heightened risk of failure.

Is it worth replacing a ballast? ›

For energy savings, reliability, and longevity – replace ballasts – not bulbs. In addition to energy efficiency issues, older ballasts simply do not offer the reflection geometry newer options do.

What causes a ballast to burn out? ›

Ballast failure is often caused by the surrounding environment—mainly heat and moisture. When it's too hot or too cold, a ballast can burn or fail to start your lamps. Heat, along with continuous condensation inside an electronic ballast, can cause corrosion over time.

How do you tell if a ballast is blown? ›

Check the Ballast with a Multimeter

Insert one probe into the wire connector while holding the white wires together. Touch the other probe to the ends of yellow, red, and blue wires coming from the ballast. Some might exclude the yellow. If the ballast doesn't cause the needle to move, you know it needs to be replaced.

Can anyone change a ballast? ›

In general, unless you have GOOD mechanical and logical skills, and can follow an electric diagram, leave it to a professional or knowledgeable colleague. Changing a ballast CAN BE demanding, even for the experienced.

Top Articles
Latest Posts
Article information

Author: Rev. Leonie Wyman

Last Updated:

Views: 5869

Rating: 4.9 / 5 (79 voted)

Reviews: 94% of readers found this page helpful

Author information

Name: Rev. Leonie Wyman

Birthday: 1993-07-01

Address: Suite 763 6272 Lang Bypass, New Xochitlport, VT 72704-3308

Phone: +22014484519944

Job: Banking Officer

Hobby: Sailing, Gaming, Basketball, Calligraphy, Mycology, Astronomy, Juggling

Introduction: My name is Rev. Leonie Wyman, I am a colorful, tasty, splendid, fair, witty, gorgeous, splendid person who loves writing and wants to share my knowledge and understanding with you.