Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (2024)

Power factor is the measure of how effectively the incoming power is used in an electrical system. A high power factor indicates that the power supplied to the electrical system is effectively used. A system with low power factor doesn’t effectively consume the incoming electric supply and results in losses. There is no power factor involved in DC circuits due to zero frequency. But, in AC circuits, the value of power factor always lies between 0 and 1.

Table of Contents
  • Power Factor Calculation
  • Leading and Lagging Power Factor
  • Unity Factor
  • Effects of Low Power Factor
  • Causes of Low Power Factor
  • Power Factor Correction
  • Frequently Asked Questions on Power Factor

Explaining Power Factor

Power factor is defined as the cosine of the angle between voltage and current. Ideally, in AC circuits, the phase difference between voltage and current is zero. But, practically there exists some phase difference between the two. The cosine of the phase difference between the two is defined as the power factor.

Power Factor Calculation

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (1)

In the figure, angle ɸ is the phase difference between the voltage and current phasor. Therefore, the power factor is:

Power Factor = cosɸ

In the figure of the power triangle,

VI sinɸ = Reactive power (in VAR)

VI cosɸ = Active power (in Watts)

VI = Apparent power (in VA)

PF = cosɸ = Active Power (W) / Apparent Power (VA)

Knowledge Review

Real Power – The power supplied to the equipment that performs useful and productive work.

Reactive Power – The power required by equipment such as transformers and motors to produce magnetic fields enabling actual work to be done.

Apparent Power – The vector sum of real power and reactive power

Power Factor can be Lagging, Leading or Unity

Lagging Power Factor

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (2)

In a circuit, when the current lags behind the voltage, then the power factor of the circuit is known as a lagging power factor. The power factor lags when the circuit is inductive. Loads such as coils, motors and lamps are inductive and have lagging pf.

Leading Power Factor

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (3)

When the current in the circuit leads the voltage, then the power factor of the circuit is said to be leading. A capacitive circuit has a leading power factor. Capacitor banks and Synchronous condensers are capacitive loads that have a leading power factor.

Unity Power Factor

The power factor is unity for ideal circuits. The power factor is unity when the current and voltage are in phase.

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (4)

Similar Reading:

Power of Alternating Current

Relation between kVA and kW

What Is Power?

Reactance and Impedance

Effects of Low Power Factor

Here are some disadvantages of low power factor:

Large Copper Losses

The copper losses are directly proportional to the square of the line current and the line current is inversely proportional to the power factor of the circuit. Combining these two relations, we understand that the copper losses will be inversely proportional to the square of power factor. When the power factor is low, the line current will be high, and consequently, the copper losses will be higher. This results in low efficiency of the power system.

Large kVA rating

Electric machines such as transformers are rated in kVA. The relationship between the power factor and the kVA rating of the machine is given by the formula below:

kVA = kW/ CosФ

From the formula, we know that the power factor of the machine is inversely proportional to its kVA rating. Larger kVA rating makes the equipment costly and heavier in size.

Poor Voltage Regulation

We already know that poor power factor results in a larger line current to be drawn by the electrical equipment. As a result, a large current at a low lagging power factor causes a higher voltage drop in transformers and alternators. This results in the decreased voltage available at the supply end of equipment and hence poor voltage regulation.

Causes of Low Power Factor

In this section, we will discuss some of the main causes of low power factor.

Harmonic Current

The presence of harmonic current reduces the power factor in the system.

Improper Wiring

Due to improper wiring or electrical accidents, an imbalance in the 3- phase power occurs which causes low power factor.

Variation in the Power System Loading

The load demand in the modern power system is not constant throughout the day. The demand is high during the morning and evening hours and the light during the rest of the day. When the system is loaded lightly, the voltage increases, increasing the magnetization current demand of the machine. This causes a poor power factor in the system.

Inductive Load

90% of the industrial loads consist of induction motors. Such machines draw magnetizing current and set up a magnetic field for its proper working and hence work at a low power factor.

The current drawn by inductive loads is lagging and results in poor power factor.

Power Factor Correction

The power factor correction can be done by the following two methods:

  • Power Factor Correction Method using Capacitors
  • Power Factor Correction Method using a Synchronous Condenser

Read More: Capacitors

Power Factor Correction by Capacitor Banks

In a three-phase system, the power factor is improved by connecting capacitors in star or delta. The star and delta connections of the capacitor banks are shown in the diagram below:

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (5)

Let,

VL be the Line voltage

Cy = capacitance per phase when the capacitor is connected in stars

CΔ = capacitor per phase when the capacitors are connected in delta

Qc = Var rating of each phase

Vp be the phase voltage

Delta Connection

For delta connection,

Vp = VL

The capacitance per phase is given by the equation:

\(\begin{array}{l}C=\frac{Q_{c}}{\omega V_{p}^2}=\frac{Q_{c}}{\omega V_{L}^2}\end{array} \)

……(eqn 1)

Star Connection

For delta connection,

\(\begin{array}{l}V_{P}=\frac{1}{3}V_{L}\end{array} \)

The capacitance per phase is expressed by the equation:

\(\begin{array}{l}C_{Y}=\frac{Q_{c}}{\omega V_{p}^2}=\frac{Q_{c}}{\omega {(\frac{V_{L}}{\sqrt{3}}})^2}=\frac{3Q_{c}}{\omega(V_{L})^2}\end{array} \)

……(eqn 2)

From equation (1) and (2) we get

\(\begin{array}{l}C_{Y}=3C_{\Delta}\end{array} \)

From equation 3, we infer the following:

  • The capacitance needed in a star connected three-phase transformer is equal to three times the capacitance required per phase when the capacitors are connected in delta.
  • The working voltage of the star connected bank is 1/√3 times the delta connected bank.

Due to the above observations, the capacitors are connected in the delta in a three-phase system for power factor improvement.

Power Factor Correction by Synchronous Condenser

Synchronous condensers are specially designed induction motors. When connected in parallel to the load, the synchronous condenser absorbs and generates the reactive power (Var) by varying the excitation of the motor field winding. Synchronous Condenser, however, has some disadvantages such as it is costly and its installation and maintenance is not easy.

Frequently Asked Questions on Power Factor

What is the power factor?

Power factor is defined as the cosine of the angle between voltage and current. Power factor is the measure of how effectively the incoming power is used in the electrical system.

How is the power factor measured?

The power factor is the cosine of the phase difference between voltage and current, and as a result, the power factor is measured using the formula Power Factor = cosɸ, where ɸ is the phase difference between the voltage and current phasor.

What are the causes of low power factor?

Some causes of low power factor are a) The presence of harmonic current in the system reduces power factor. b) Improper wiring leads to three-phase imbalance causing low power factor. c) When the system is loaded lightly, the voltage increases, increasing the magnetization current demand of the machine. This causes a poor power factor in the system. d) The current drawn by inductive loads is lagging and results in a poor power factor.

What are the effects of low power factor?

Some effects of low power factor are as follows: a) Large Copper Losses b) Large kVA rating c) Poor Voltage Regulation.

What is the low power factor correction?

Low power factor correction is a method of improving the power factor and therefore, improving the power quality. The low power factor can be corrected using a) capacitor banks and, b) Synchronous Condenser.

Stay Tuned to BYJU’S and Fall in Love with Learning!

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF (2024)

FAQs

Power Factor - Explanation, Low Power Factor Correction, Causes of Low PF? ›

Some causes of low power factor are a) The presence of harmonic current in the system reduces power factor. b) Improper wiring leads to three-phase imbalance causing low power factor. c) When the system is loaded lightly, the voltage increases, increasing the magnetization current demand of the machine.

What causes power factor correction? ›

Power factor correction is achieved by the addition of capacitors in parallel with the connected motor or lighting circuits and can be applied at the equipment, distribution board or at the origin of the installation.

What are the 3 types of power factor? ›

There are mainly three categories of power:
  • Real Power – It is the average of the instantaneous product of voltage and current. ...
  • Apparent Power – The product of rms current and voltage is called as apparent power. ...
  • Reactive Power – It is the power required by transformers or motors to produce magnetic fields.

What is the PFC explained? ›

Power factor correction (PFC) is the set of mechanisms built into a power supply circuit to raise the power factor (PF). PFC is commonly incorporated into computer power supplies to increase their PF. A circuit's PF is the ratio of real power to apparent power.

How the low power factor PF can be improved in AC circuits? ›

You can improve power factor by using power factor correction (PFC) devices, such as capacitors, reactors, or filters. These devices are connected in parallel or series with your loads and compensate for the reactive power in the circuit. They can be fixed or variable, depending on the type and variation of your loads.

What are the causes of low power factor correction? ›

Some causes of low power factor are a) The presence of harmonic current in the system reduces power factor. b) Improper wiring leads to three-phase imbalance causing low power factor. c) When the system is loaded lightly, the voltage increases, increasing the magnetization current demand of the machine.

What happens if power factor is low? ›

If the power factor is low, the increased current will increase the copper losses (I2R) in the transformer, transmission line, and load. Poor voltage regulation: If the power factor is low, large line current is drawn, which causes a voltage drop in the generator, transformer, and transmission line.

What is the most common power factor? ›

In most cases, commercial buildings have a power factor rated between 0.98 and 0.92, while most industries fall below 0.7.

What does a power factor of 0.8 mean? ›

A common industry standard generator power factor rating is 0.8, or 80%, meaning these loads can use 80% of the generator's power supply. A majority of the time, generators that use a Power Factor (or PF for short) that have a power factor rating of 0.8 are 3-phase generators.

What is the formula for PF in electrical? ›

PF = kW / kVA

A steel stamping operation runs at 100 kW (Working Power) and the Apparent Power meter records 125 kVA. To find the PF, divide 100 kW by 125 kVA to yield a PF of 80%. This means that only 80% of the incoming current does useful work and 20% is wasted through heating up the conductors.

What does PFC protect against? ›

Why are PFCs used in outdoor gear? Some types of PFC are exceptionally good at repelling water, dirt and oil. As a result, they became widely used in durable water repellent (DWR) treatments for outdoor clothing and equipment.

What is power factor and why is it important? ›

Power Factor is the ratio of Working Power to Apparent Power. All motors which come in the form of a machine, such as conveyors, mixers, compressors, lifts and escalator all have an efficiency rating known as a Power Factor. It is a measure of “efficiency” and has values ranging from 0 to 1, where 1 is 100% efficient.

How can low power factor be avoided? ›

Consumers can avoid power factor penalties by installing devices for power factor correction, Install capacitors in the distribution system. While capacitor banks improve the overall system's power factor, the individual machines which caused a drop in power factor would still remain the same.

How do you compensate for low power factor? ›

There are several methods used for power factor correction. The 2 most used are capacitor banks and synchronous condensers. Capacitor banks are systems that contain several capacitors used to store energy and generate reactive power. Capacitor banks might be connected in a delta connection or a star(wye) connection.

What are the methods of improving PF? ›

Blog
  • Use Of Static Capacitors. The first amongst the several power factor improvement methods is to use static capacitors; these capacitors have the potential to control the current lagging effects. ...
  • Use Of Synchronous Condenser. ...
  • Use Of Phase Advancer. ...
  • Conclusion.
Feb 15, 2021

What are the ways for power factor correction? ›

There are several methods used for power factor correction. The 2 most used are capacitor banks and synchronous condensers. Capacitor banks are systems that contain several capacitors used to store energy and generate reactive power. Capacitor banks might be connected in a delta connection or a star(wye) connection.

How do you increase power factor correction? ›

What can I do to improve power factor? You can improve power factor by adding power factor correction capacitors to your plant distribution system. When apparent power (kVA) is greater than working power (kW), the utility must supply the excess reactive current plus the working current .

How do capacitors correct power factor? ›

A capacitor corrects the power factor by providing a leading current to compensate the lagging current. Power factor correction capacitors are designed to ensure that the power factor is as close to unity as possibe.

What are the devices used in power factor correction? ›

Power Factor Correction works by using capacitors and inductors. A capacitor is a device that stores energy in an electric field, while an inductor is a device that stores energy in a magnetic field. By adding these devices to circuits alongside your switchgear, PFC can help to improve the power factor.

Top Articles
Latest Posts
Article information

Author: Duane Harber

Last Updated:

Views: 5456

Rating: 4 / 5 (51 voted)

Reviews: 90% of readers found this page helpful

Author information

Name: Duane Harber

Birthday: 1999-10-17

Address: Apt. 404 9899 Magnolia Roads, Port Royceville, ID 78186

Phone: +186911129794335

Job: Human Hospitality Planner

Hobby: Listening to music, Orienteering, Knapping, Dance, Mountain biking, Fishing, Pottery

Introduction: My name is Duane Harber, I am a modern, clever, handsome, fair, agreeable, inexpensive, beautiful person who loves writing and wants to share my knowledge and understanding with you.