Rules of Thumb for Troubleshooting (2024)

Rules of Thumb for Troubleshooting (1)

Normal chilled water supplytemperatures in the range of 45 - 55 degrees Farenheit. This is the correct range of chilled water supply temperatures for comfort cooling. Normal hot water supply temperature is in the range of 100 - 150 degrees Farenheit.

Rules of Thumb for Troubleshooting (2)

One cfm per square foot of floor area is the average air quantity required for a room or entire building.

Rules of thumb are abbreviated short cuts, time savers, and approximations. Each is a quick estimation of what most systems should do most of the time, but remember that none of these numbers are infallible.

The rules are not cast in concrete. They do not always apply to every system, nor do they work in every circ*mstance. It is expected that the technician using them is a professional who can use reason and exercise caution in their application.

Rules of thumb usually assume certain normal design and operating criteria, which are not always present.

The rules are not to be used for system design purposes. Rather, they are the result of carefully studying good system designs. Technicians and engineers, however, can benefit from using them as tools for estimating and solving operational problems.

Here are some common hvacr rules of thumb.

AIRFLOW

Air quantities (cfm):

  • 400 cfm per ton of cooling is needed for normal comfort applications, 500 cfm per ton of cooling for heat pump and high sensible heat applications, and 350 cfm per ton of cooling for high latent heat applications.
  • These are the approximate amounts of air that should be moving through evaporators for three common applications. Say, for example, you have a comfort cooling application at a savings and loan office that has a 10-ton system. Therefore, you multiply 10 tons by 400 cfm per ton to reveal the total system airflow requirement of 4,000 cfm under normal operating conditions.

  • One cfm is needed per square foot (1 cfm/sq ft) of floor area.
  • This is the average air quantity required for a room or an entire building. This number is based upon an averaged heat load calculation for comfort cooling. There is an assumption of an 8-ft ceiling, no unusual window areas, and average insulation. This rule of thumb provides about 7.5 air changes per hour.

    This rule is a quick way to approximate the cooling load for a room or building and may be helpful in estimating room air quantities. For example, to estimate the number of tons required to cool a 1,600-sq-ft home, multiply 1,600 by 1 cfm/sq ft to get 1,600 cfm of air. Using the 400-cfm/ton rule, divide 1,600 cfm by 400 cfm/ton to get 4 tons of required cooling.

  • Six to 10 air changes are needed per hour.
  • This is the average number of times in each hour that the air in the building or room (assuming 7- to 8-ft ceilings) is removed and replaced by circulating the air.

    Air velocities (fpm):

  • 700 to 750 fpm are needed for disposable filters; 250 fpm for HEPA filters; and 500 fpm for electronic air cleaners.
  • These are the recommended air speeds for filters. Speeds higher than these will decrease filtering efficiency.

  • 550 to 600 fpm maximum and 400 fpm minimum are needed for evaporators; 1,000 fpm for condensers; and 700 fpm for hot water coils.
  • These are the recommended velocities for coils. Speeds faster than these may cause condensation to be blown off of the evaporator fins and down the duct. Speeds slower than 400 fpm may cause the evaporator to freeze over.

    Terminal velocities are the velocities at the end of the run, such as registers or diffusers, where the air enters a room.

  • Bypass air should be at a rate of 0.1 to 0.35, or 10% to 35%.
  • This is the average percentage of air that bypasses or fails to come into contact with the evaporator as it passes through the evaporator. The higher the air speed in fpm, the higher the bypass factor. High bypass factors are normally found on heat pumps in the heating cycle, and on high sensible heat applications like computer room systems. Low bypass factors are found on high latent heat applications, such as those found in restaurants (especially cooking areas) and bowling alleys.

    BUILDING AIR PRESSURE

    Building air pressure is normally between 0.03 to 0.05 in. of static pressure. Infiltration air leaks into a building from the outside, such as through doors and cracks around windows. This infiltrating air is unfiltered and untreated.

    To prevent infiltration, a building is kept at a slightly positive air pressure. This is accomplished by adjusting the outside air dampers so they are open slightly more than the exhaust air dampers. Building air pressure measurements should be taken whenever an adjustment is made.

    Rules of Thumb for Troubleshooting (3)

    The thermoststic expansion valve controls evaporator superheat, which means it controls the amount of liquid refrigerant boiling in the evaporator.

    REFRIGERATION AND A/C

  • There is one horsepower (1 hp) for each ton of cooling. It takes a l-hp compressor to provide 1 ton of comfort cooling. Therefore, a 25-ton system has a 25-hp compressor motor.
  • Note:This applies to comfort cooling only. A lower-suction-pressure application such as refrigeration will have a higher hp/ton ratio. The lower the suction pressure, the higher the hp/ton required.

  • Thermostatic expansion valve superheat should be 8° to 12°F.
  • The valve controls evaporator superheat, which means it controls the amount of liquid refrigerant boiling in the evaporator. The lower the superheat, the more liquid in the evaporator.

    However, superheat that is too low can cause the valve to lose control of the superheat altogether. The valve only controls evaporator superheat. If the valve is properly controlling superheat, do not adjust it to change evaporator temperature or pressure.The valve is not an evaporator temperature or pressure control, so do not attempt an adjustment without measuring the superheat. The 8° to 12° superheat is normal for air conditioning systems. Low-temperature systems often use different valves and lower superheat settings.

    Remember, superheat is a temperature differential, not a single temperature measurement.

    Normal system superheat is 20° to 30°. System superheat is not the same as thermostatic expansion valve superheat. System superheat consists of the temperature differential from the point in the evaporator where all the refrigerant has changed to a gas to the suction line — about 6 in. from the compressor service valve.

    Normally, charged and operating systems will have a system superheat of 20° to 30°. System superheat greater than 30° may indicate that the low side of the system is starved for refrigerant. System superheat less than 20° may indicate that the low side is overcharged.

    Again, system superheat is a temperature differential, not a single temperature measurement. The valve superheat is part of the system superheat.

  • High-side subcooling is 5° to 15°.
  • Refrigerant in the condenser changes from a gas to a liquid and then begins to subcool. Subcooling takes place in the bottom of the condenser and in the liquid line. The amount of subcooling taking place in the condenser is 5° to 15°. It is never greater than 15°.

    Since only liquid subcools, the amount of subcooling is an indication of the amount of liquid in the high side of the system. Overcharged systems have higher-than-normal amounts of subcooling. Undercharged systems have low subcooling.

    Comparing high-side subcooling and low-side system superheat will usually solve most refrigeration cycle problems of overcharge, undercharge, and restrictions.

  • Normal evaporator air temperature drop is 18° to 20°.
  • Measuring the temperature drop, or difference of the air as it moves through the evaporator, is one method of approximating correct airflow. Assuming 400 cfm per ton of cooling, when the airflow is correct there will be an 18° to 20° drop in air temperature.

    Abnormally low airflow will remain in contact with the evaporator longer, and will be chilled to a lower temperature and greater temperature difference.

  • Normal condenser air temperature rise is not to exceed 30°.
  • Lack of air over the condenser results in high head pressure, lower system capacity, and increased power consumption. Air is heated as it passes through the condenser.

    Low air across a condenser is indicated by an air temperature rise greater than 30°. The smaller quantity of air over the condenser must absorb the same amount of heat; therefore, the temperature rise is greater.

    WATER

  • For chilled and condenser water, the expected temperature drop or rise is normally 8° to 10°. Just like air, water has a temperature drop or rise as it is cooled or heated. As a chiller cools water, the number of gallons per minute (gpm) circulated determines the number of degrees of drop.
  • The same is true for a water-cooled condenser. An 8° temperature change is proportional to about 3.9 gpm circulated per ton. A 10° change is proportional to about 2.4 gpm circulated per ton.

    For example, if a 25-ton system has a chilled water temperature differential of 8°, then 25 tons times 3.9 gpm/ton gives a total estimate of the chilled water flow of 97.5 gpm.

  • Normal chilled water supply temperature is in the range of 45° to 55°. This is the correct range of chilled-water supply temperatures for comfort cooling.
  • Normal hot water supply temperature is in the range of 100° to 150°. This is the correct range of hot water supply temperatures for hot water comfort heating or reheat. Systems that require hot water temperatures over 150° usually have a low flow rate problem.
  • Christopherson is an hvac instructor at San Jose City College, San Jose, CA.

    Publication date: 02/05/2001

    Rules of Thumb for Troubleshooting (2024)

    FAQs

    What is the CFM formula? ›

    CFM = (fpm * area), where fpm is the feet per minute. To find the cubic feet per minute, substitute the FPM value with the area after the area is squared.

    What is the thumb rule for AC tonnage calculation? ›

    For example, one commonly used rule of thumb for general office areas is that the cooling load is 200-300 square feet of floor area per ton of cooling. For data centers, the cooling load is 150-300 square feet per ton of cooling.

    How much airflow should be coming out of vent? ›

    Example: For residential bathrooms up to 100 sq. ft. in area, HVI recommends an exhaust rate of 1 cfm per square foot. A bathroom is 6′ to 10′ or 60 square feet.

    How many CFM do I need to cool a room? ›

    However, a general guideline can be found below if you do not have the room's exact dimensions at this time: Under 200 square feet: 2,000 to 3,000 CFM. 200 to 300 square feet: 3,000 to 4,000 CFM (typically a standard bedroom or kitchen) 300 to 450 square feet: 4,000 to 6,000 CFM (usually a master bedroom or living room ...

    How many CFM is 100 PSI? ›

    While small, mobile at-home air compressors may deliver around 2 CFM, industrial air compressors with 200 HP can achieve air flow of around 1,000 CFM at 100 PSI.

    What is the difference between CFM and CFM? ›

    CRM platforms track customer interactions, whereas SCM platforms track materials and product shipments. Tech buyers should know how these platforms differ before making a purchase. While CRM platforms can help organizations drive sales, a supply chain management platform helps land those sales.

    What happens if I put a 1.5 ton AC instead of 2 ton in a room the size of about 200 sq ft? ›

    If the unit capacity is too much, the AC will not run a complete cycle and constantly switch, increasing an individual's electricity bill every month. Likewise, units that are too small will run relentlessly and consume more electricity.

    What is the 20 degree rule air conditioners? ›

    You may have heard someone mention “the 20 degree rule” when it comes to your air conditioning unit. But what does that mean? Simply put, it means you should never set your thermostat for a temperature more than 20 degrees cooler than the outside air.

    How many square feet will a 2 ton AC cool? ›

    For those of you that don't understand the way AC systems work, a 2-ton unit typically provides cooling for about 900-1,400 square feet of space – give or take.

    What is a common mistake in ductwork installation? ›

    Common HVAC Installation Mistakes and How to Avoid Them
    • Picking the Wrong HVAC System. It is the most common mistake made by first-time HVAC buyers. ...
    • Wrong Thermostat Placement. ...
    • Inadequate Ductwork Sealing. ...
    • Wrong Vent Placement and Installation. ...
    • Inadequate Condenser Clearance.

    What happens if there is not enough return air? ›

    If there is not enough return air available, your HVAC system will not heat or cool properly. They must be properly sized — Return air ducts must be large enough to carry a sufficient amount of expended air back to your furnace, air conditioner, or heat pump.

    Why is air barely coming out of vents? ›

    When the AC filters are clogged with dirt, hair, dust, and other debris, the airflow through the vents in your home may be reduced, decreasing the efficiency of your air conditioning system. This can also happen if the AC filters are blocked by some furniture placed right in front of the system.

    How many CFM do I need for a 12x12 bathroom? ›

    The rule of thumb is that you need at least 1 CFM per square foot of room area.

    Is it better to have more CFM or less? ›

    A higher CFM is always better for your kitchen fan. You can always run a high CFM hood on lower settings. It provides great ventilation by moving a heavy amount of air per minute. If you cook often or enjoy Asian cooking, a high powered fan is essential to keep grease out of your kitchen exhaust system.

    Does adding more fans increase CFM? ›

    Stacking fans directly on top of each other generally increases turbulence, static pressure, and cost without having a definite positive impact on CFM and cooling. Ideas to increase CFM would include: Purchase a fan that has more CFM.

    How many CFM can a 3 8 hose handle? ›

    3/8″ = 2.5 to 3.5 cfm.

    What is difference between CFM and SCFM? ›

    SCFM and CFM are both essential values that indicate the airflow rate in a compressor. SCFM measures this value based on 'ideal' temperature and pressure conditions, while CFM measures the 'actual' air flow rate.

    How many CFM is a 3 ton? ›

    A 3-ton heat pump has approximately 1200 CFM of air flow.

    What does 90 PSI SCFM mean? ›

    By calculating how much pressure you need for your application, you can verify you are working with the right air compressor by finding out its SCFM. An air compressor with 10 horsepower or more should generate around 3 or 4 cubic feet of air per minute at 90 PSI.

    Is PSI same as CFM? ›

    The difference between PSI and CFM is what they measure. PSI measures pressure, while CFM measures volume. PSI and CFM are performance specifications for air compressors and air-powered machinery. Together, they indicate the maximum air volume and pressure produced by an air compressor to power air tools.

    How many CFM do I need for 200 square feet? ›

    Step 1: Calculate Bathroom Size: 20' x 10' Bathroom = 200 square feet. Result: You will need a 150 CFM fan for this bathroom.

    Should I go for a 1 ton or a 1.5 ton AC for my 120 sq foot room? ›

    One of the most significant factors you should keep in mind is the AC's capacity based on the size of the room you're going to fit in. For a room sized around 100 to 120 square feet, a 1-ton capacity Air conditioner should be sufficient enough. For bigger rooms, you should buy a 1.5-ton or a 2-ton Air Conditioner.

    Should you oversize your AC unit? ›

    An oversized HVAC unit can make your home's inside temperature uncomfortable. An HVAC system with excess capacity can heat or cool your home faster, but that speed often results in a couple of other issues. First, your home won't benefit from gradual, even heating and cooling.

    What happens if room is too big for AC? ›

    If an air conditioner is too large for the space it is installed in, then it will have too much power for your home. This may not seem detrimental, however this actually causes the thermostat to shut down the AC system before it has had a change to complete its full cycle—a process called short-cycling.

    Will my AC go to 65 degrees when its 100 degrees out? ›

    Your AC doesn't work that way

    If it's over 100 degrees outside, we're sorry to say your home will never be less than 80 degrees. Why? Because your AC is only designed to cool your home to about 15 to 20 degrees less than the outside temperature.

    Is 72 too cold for AC? ›

    When setting your thermostat, most homeowners find 72 is a good temperature for air conditioning. However, you may need to adjust that setting based on weather conditions. The bigger the difference between indoor and outdoor temperatures, the higher your energy bill will be.

    How long should it take to cool a house from 80 to 72? ›

    It usually takes around two and a half to three and a half hours to cool your house from 80 to 72 degrees. However, a variety of different factors can affect the time it takes to reach the desired temperature, including the thermostat setting, the size of the house, and the efficiency of the air filters.

    Is Trane or carrier better? ›

    There is no difference in terms of basic and mid-level units of both the brands when it comes to deciding the superiority in terms of quality. However, if you are looking forward to buying a top-line model, then you must go with Trane as it has a better warranty on their compressors.

    How many ton AC do I need for 1500 sq ft? ›

    Benchmarks for Air Conditioner Size:

    1,201 to 1,500 square feet homes should use 2.5 tons. If your home size is higher than the number above but is less not more than 1,800 square feet, you can go for a three-ton A/C.

    How many vents should a 2.5 ton AC unit have? ›

    For instance a 2.5 ton system (Approximately 400 CFM per ton) would require (2) 14” flexible return ducts or (1) very short flexible 18” duct to move the 1000 CFM required by the 2.5 ton system.

    What is the most common problem HVAC system? ›

    The most common cause is a dirty air filter. When the air filter is dirty your blower has to work harder to force air through the filter. This increases the blower's energy consumption and can sometimes trip the circuit breaker. Check your filter and replace it with a clean one before resetting your circuit breaker.

    What is the most common cause of poor air flow in a duct system? ›

    Obstructed Vent

    One of the most common causes for poor airflow is a blocked vent. To properly heat or cool your home, the air needs to be unobstructed. To see if there are any blocked vents, look by the baseboards or on the ceiling. Furniture, bedding, and the vent damper could all be possible obstacles to the vent.

    What causes the most leaks in ductwork? ›

    Temperature fluctuations, high humidity, and vibrations due to air circulation cause the wear and tear. Over time, the seals can deteriorate, the duct material can corrode, and the duct joints can disengage. Pests that find their way into the duct system can also cause damage.

    How do I get more air flow from my vents? ›

    5 Ways to Improve AC Airflow for Better Efficiency
    1. Unblock AC Vents. Your AC system flows in a circular pattern. ...
    2. Clean AC Vents. AC vents tend to accumulate dust and debris floating in your house. ...
    3. Check Your Filters. ...
    4. Find and Fix Leaks. ...
    5. Schedule Regular HVAC Maintenance.
    Sep 11, 2019

    Can HVAC have too much return air? ›

    Can You Have Too Much Return Air? Too much return air coming through your system isn't much of an issue because the fans and ductwork working to get that air back into the system only pull with so much force to make the HVAC system work correctly.

    How do I increase airflow in my ductwork? ›

    5 Ways to Improve Airflow in Your Home
    1. Check Vents and Registers. One of the simplest things you can do to increase airflow in your home is to check the vents and registers in each room. ...
    2. Turn on Ceiling Fans. ...
    3. Schedule HVAC Maintenance. ...
    4. Consider Duct Cleaning. ...
    5. Invest in a Ventilator.
    Jul 24, 2017

    How do you tell if your AC vents are clogged? ›

    How to Know if Your Air Ducts Are Clogged
    1. Temperatures varying drastically between rooms.
    2. Dirty air coming from vents.
    3. Unusual spikes in electric bills.
    4. Air is not coming out of some vents in your house.
    5. Air coming from vents is warm.

    Can you have too much CFM in bathroom? ›

    Yes, you can oversize your bathroom exhaust fan. In fact, in most cases, it's a good idea to do so! Remember how we talked about the minimum CFM requirement being 50 CFM? Well, even though that may be the code requirements, you'll likely want a bathroom exhaust fan with more power than that.

    Can a bathroom fan be on a 15 amp circuit? ›

    General lighting/fan circuit required: Each bathroom should have a circuit for lighting and an exhaust fan. According to the Code, this circuit may be a 15-amp circuit if it serves just lighting, but it should be a 20-amp circuit if it is also serving a vent fan.

    Are you supposed to shower with the fan on? ›

    How long should the fan be running? You should turn on the fan as soon as you turn on the shower or bath water. Additionally, leave the fan on for about 20 minutes after you're finished bathing. This will help keep your bathroom free of moisture and mold.

    What is the best airflow configuration? ›

    If you only have two fans, we recommend positioning them in a front, rear configuration. If you have three fans and a dedicated GPU, we recommend placing them in the front, rear, and bottom of your case.

    What happens if CFM is too low? ›

    Too little CFM and you won't be able to run your tools continuously—or at all—and too much CFM could mean you've overspent on your air compressor!

    What size fan moves the most air? ›

    The strongest ceiling fans offer 10,000 CFM, but an average room only needs 5,000 to 6,500. Smaller spaces will need even less than that. Because the blade span and pitch impact how cool a room feels, you should also consider the wind speed factor, which measures how fast the air is moving.

    What is a good CFM airflow? ›

    Energy Information

    On high speed: Good CFM ranges from 4,000 to 5,000. Better ranges from 5,000 to 6,000. Best is over 6,000.

    How do you calculate the airflow of a CFM? ›

    To calculate Air Flow in Cubic Feet per Minute (CFM), determine the Flow Velocity in feet per minute, then multiply this figure by the Duct Cross Sectional Area.

    How many CFM do I need for a 12x12 room? ›

    One cfm is needed per square foot (1 cfm/sq ft) of floor area. This is the average air quantity required for a room or an entire building.

    How many CFM do I need for 1000 square feet? ›

    Heat and energy recovery ventilators
    Total area of home (square feet)Continuous ventilation rate
    1,000 square feet50 CFM
    2,000 square feet100 CFM
    3,000 square feet150 CFM

    How do I calculate cubic feet from CFM? ›

    How to calculate required CFM for a room?
    1. Measure the room's length and breadth and also its height.
    2. Multiply the 3 measurements and get the cubic footage of the room.
    3. Multiply the cubic volume of the room by the number of times you want the air to turn over or exchange within an hour.
    Jul 7, 2022

    Does more CFM mean more airflow? ›

    CFM, or cubic feet per minute, measures the volume of air that a fan moves. The larger the number, the more air it can move. Bathroom fans, range hoods, carburetors, air compressors, commercial fans, and more measure airflow in CFM.

    Is airflow the same as CFM? ›

    CFM stands for cubic feet per minute. Also referred to as airflow, the CFM is how much air a fan moves. When the ceiling fan is at its highest speed, the measurement is taken using both the volume of air and the rate at which it moves.

    Is 80 CFM better than 50 CFM? ›

    For medium-sized bathrooms, use 80 to 99 CFM bath fans. For large bathrooms that are over 100 square feet but under 150 square feet, use over 100 CFM bath fans. For extra-large bathrooms, add 50 CFM for every toilet, 50 CFM for every bathtub or shower and 100 CFM for a jetted bathtub.

    How many square feet is 50 CFM good for? ›

    Ventilation rates based upon eight air changes per hour are generally suggested. For most bathrooms this works out to one CFM per square foot of bathroom area. For example, a 7' x 10' bathroom would require a 70 CFM fan. A 50 CFM rating is recommended as a minimum for bathrooms 50 sq.

    What CFM is the rule of thumb for a 2.5 ton unit? ›

    If we stick to the 400 CFM per ton rule, then that would mean this 2.5-ton air conditioner would need 1,000 CFM of air. Using this example, we have a 75°F indoor dry-bulb temperature.

    How many CFM is a 2 ton? ›

    For optimum performance, most manufacturers recommend that 400 cfm per ton of air conditioning should be used. For example, a 2-ton system should have 800 cfm of air moving through the evaporator coil.

    How do you calculate airflow? ›

    Determining air flow is a matter of multiplying the cross sectional area of a duct by the air velocity. If the dimensions of the duct are known, then the cross-sectional area can be easily determined and the volumetric flow calculated.

    How many CFM do I need for 500 square feet? ›

    200 cfm 400 cfm

    How many CFM is a 5 ton unit? ›

    A 5-ton system should have have 2,000 cfm, a 6-ton system should have 2,400 cfm, and so on and son. Measuring how much airflow measurements deviate from that math is a quick way to diagnose airflow issues in a residential duct system.

    How do you calculate CFM to BTU? ›

    It is simply CFM x Delta-T x 4.5. In other words, total BTU equals delivered airflow (cfm) times the change in temperature and moisture content of the air through the system (Delta-T), times the constant of 4.5.

    Top Articles
    Latest Posts
    Article information

    Author: Mrs. Angelic Larkin

    Last Updated:

    Views: 5638

    Rating: 4.7 / 5 (47 voted)

    Reviews: 86% of readers found this page helpful

    Author information

    Name: Mrs. Angelic Larkin

    Birthday: 1992-06-28

    Address: Apt. 413 8275 Mueller Overpass, South Magnolia, IA 99527-6023

    Phone: +6824704719725

    Job: District Real-Estate Facilitator

    Hobby: Letterboxing, Vacation, Poi, Homebrewing, Mountain biking, Slacklining, Cabaret

    Introduction: My name is Mrs. Angelic Larkin, I am a cute, charming, funny, determined, inexpensive, joyous, cheerful person who loves writing and wants to share my knowledge and understanding with you.